INTRODUCTION:
Aerial Bunched Cables (ABC) is a very novel concept for Over Head Power distribution. When compared to the conventional bare conductor over head distribution system. ABC provides higher safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost. This system is ideal for rural distribution and specially attractive for installation in difficult terrains such as hilly areas, forest areas, coastal areas etc.

 
 LT Aerial Bunched Cables 1100 Volts (3.5 Core). Reference standard: Generally to IS :  7098(1) 88.

Sl. No.

Description

3 x 25
+
1 x 16
+
1 x 35

3 x 35
+
1 x 16
+
1 x 35

3 x 50
+
1 x 25
+
1 x 35

3 x 70
+
1 x 35
+
1 x 35

3 x 95
+
1 x 50
+
1 x 55

1. Power/Neutral Core :          
1.1 Conductors          
 

Nom. Cross sectional area
(i) Power cores (mm2)
(ii)Neutral cores (mm2)

25
16

35
16

50
25

70
35

95
50

  Max. D.C. resistance conductor at 20ºC
(i) Power cores (Ohm/Km)
(ii) Neutral cores (Ohm/Km)
1.20
1.91
0.868
1.910
0.641
1.200
0.443
0.868
0.320
0.641
  Approx. diameter of conductor
(i)Power cores (mm)
(ii)Neutral cores (mm)
6.2
5.1
7.3
5.1
8.35
6.20
10.1
7.30
12.00
8.35
1.2 Insulation:
Minimum thickness:
(i)Power cores (mm)
(ii)Neutral cores (mm)
0.9
0.7
0.9
0.7
1.0
0.9
1.1
0.9
1.1
1.0

2.

Messenger Wire(Bare):
(i) Nom. Cross sectional area (Sq. mm)
(ii) Approx. Breaking load (KN)

35
41

35
41

35
41

55
62

55
62

3.

Current Rating:
Continuous current carrying
capacity of cable in Air at
Ambient temp. 40ºC (Amp.)

99

122

149

190

235

4.

Approx. weight (Kg./Km.)

580

665

810

1165

1430

5.

Number of Cores:
(i)Power cores
(ii)Neutral cores
(iii) Bare messenger

(No.)    :  3
(No.)    :  1
(No.)    :  1

6.

De-rating factor
De-rating factors for variation in Air Temp.
Air Temp. (ºC) Rating Factor
30 35 40 45 50 55
1.12 1.06 1.0 0.94 0.88 0.83

7.

(i) Identification of power core :
(ii) Laying :

By providing ridges on the insulation:
Three power cores and one Neutral core shall be suitable twisted around bare Steel Messenger./AAAC 

8.

Detail of the Power / Neutral core :
(i) Conductor:
a) Material
(b) Flexibility class as per IS:8130/84
(c) Form of Conductor
(ii) Insulation:
(a) Material
(b) Colour of Insulation

Aluminium to IS:8130/84
Class – 2
Compacted circular.

Cross linked Polyethylene to IS: 7098(I)/88
Black

9.

Details of the Messenger wire (Bare)
(i) Material
(ii) Form of Conductor

ACSR/AAAC Conductor to IS:398(II) & (IV) respectively.

Standard circular/ compacted circular.


Top
 LT Aerial Bunched Cables 1100 Volts (4 Core). Reference standard: Generally to IS :  7098(1) 88.

Sl. No.

Description

3 x 25
+
1 x 25
+
1 x 35

3 x 35
+
1 x 35
+
1 x 35

3 x 50
+
1 x 50
+
1 x 35

3 x 70
+
1 x 70
+
1 x 55

3 x 95
+
1 x 95
+
1 x 55

1. Power/Neutral Core :          
1.1 Conductors          
 

Nom. Cross sectional area
(i) Power cores (mm2)
(ii)Neutral cores (mm2)

25
25

35
35

50
50

70
70

95
95

  Max. D.C. resistance conductor at 20ºC
(i) Power cores (Ohm/Km)
(ii) Neutral cores (Ohm/Km)
1.20
1.20
0.868
0.868
0.641
0.641
0.443
0.443
0.320
0.320
  Approx. diameter of conductor
(i)Power cores (mm)
(ii)Neutral cores (mm)
6.2
6.2
7.3
7.3
8.35
8.35
10.1
10.1
12.00
12.00
1.2 Insulation:
Minimum thickness:
(i)Power cores (mm)
(ii)Neutral cores (mm)
0.9
0.9
0.9
0.9
1.0
1.0
1.1
1.1
1.1
1.1

2.

Messenger Wire(Bare):
(i) Nom. Cross sectional area (Sq. mm)
(ii) Approx. Breaking load (KN)

35
41

35
41

35
41

55
62

55
62

3.

Current Rating:
Continuous current carrying
capacity of cable in Air at
Ambient temp. 40ºC (Amp.)

99

122

149

190

235

4.

Approx. weight (Kg./Km.)

610

725

880

1270

1570

5.

Number of Cores:
(i)Power cores
(ii)Neutral cores
(iii) Bare messenger

(No.)    :  3
(No.)    :  1
(No.)    :  1

6.

De-rating factor
De-rating factors for variation in Air Temp.
Air Temp. (ºC) Rating Factor
30 35 40 45 50 55
1.12 1.06 1.0 0.94 0.88 0.83

7.

(i) Identification of power core :
(ii) Laying :

By providing ridges on the insulation:
Three power cores and one Neutral core shall be suitable twisted around bare Steel Messenger./AAAC 

8.

Detail of the Power / Neutral core :
(i) Conductor:
a) Material
(b) Flexibility class as per IS:8130/84
(c) Form of Conductor
(ii) Insulation:
(a) Material
(b) Colour of Insulation

Aluminium to IS:8130/84
Class – 2
Compacted circular.

Cross linked Polyethylene to IS: 7098(I)/88
Black

9.

Details of the Messenger wire (Bare)
(i) Material
(ii) Form of Conductor

ACSR/AAAC Conductor to IS:398(II) & (IV) respectively.

Standard circular/ compacted circular.

Top

 LT Aerial Bunched Cables 1100 Volts (5 Core) with Street Lighting Conductor.  Reference standard: Generally to IS : 6474-71.

Sl. No.

Description

3 x 16
+
1 x 16
+
1 x 25

3 x 25
+
1 x 16
+
1 x 25

3 x 50
+
1 x 16
+
1 x 25

3 x 50
+
1 x 16
+
1 x 35

3 x 70
+
1 x 16
+
1 x 50

3 x 95
+
1 x 16
+
1 x 70
3 x 120
+
1 x 16
+
1 x 70
1. Power/Neutral Core :              
1.1 Conductors              
 

Nom. Cross sectional area
(i) Power cores (mm2)
(ii)Neutral cores (mm2)

16
16

25
16

35
16

50
16

70
16

95
16
120
16
  Max. D.C. resistance conductor at 20ºC
(i) Power cores (Ohm/Km)
(ii)Neutral cores (Ohm/Km)
1.91
1.91
1.20
1.91
0.868
0.910
0.641
0.910
0.443
0.910
0.320
1.910
0.253
1.910
  Approx. diameter of conductor
(i)Power cores (mm)
(ii)Neutral cores (mm)
4.4
4.4
5.5
4.4
6.8
4.4
7.9
4.4
9.6
4.4
11.3
4.4
12.7
4.4
1.2 Insulation:
Minimum thickness:
(i)Power cores (mm)
(ii)Neutral cores (mm)
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.0
1.4
1.0
1.4
1.0
1.6
1.0

2.

Messenger Wire(Bare):
(i) Nom. Cross sectional area (Sq. mm)
(ii) Approx. Breaking load (KN)

25
7.5

25
7.5

25
7.5

35
10.3

50
14.7

70
2.06
70
20.6

3.

Current Rating:
Continuous current carrying
capacity of cable in Air at
Ambient temp. 40ºC (Amp.)

51

70

86

105

130

155 180

4.

Approx. weight (Kg./Km.)

610

725

880

1270

1570

1180 1430

5.

Number of Cores:
(i)Power cores
(ii)Neutral cores
(iii) Bare messenger

(No.)    :  3
(No.)    :  1
(No.)    :  1

6.

De-rating factor
De-rating factors for variation in Air Temp.
Air Temp. (ºC) Rating Factor
30 35 40 45 50 55
1.12 1.06 1.0 0.94 0.88 0.83

7.

(i) Identification of power core :
(ii) Laying :

By providing ridges on the insulation.
Three power cores and one Neutral core shall be suitable twisted around bare AAAC Messenger.

8.

Detail of the Power / Neutral core :
(i) Conductor:
a) Material
(b) Flexibility class as per IS:8130/84
(c) Form of Conductor
(ii) Insulation:
(a) Material
(b) Colour of Insulation

Aluminium to IS:8130/84
Class – 2
Compacted circular.

High Density Polyethylene to IS: 6474 - 1971
Black

9.

Details of the Messenger wire (Bare)
(i) Material
(ii) Form of Conductor

All Alloy Aluminium Conductor to IS:398 (IV).
Standard Compacted circular.

Top

 LT Aerial Bunched Cables 1100 Volts (4 Core). Reference standard: Generally to IS :  6474 - 71.

Sl. No.

Description

3 x 16
+
1 x 25

3 x 25
+
1 x 25

3 x 35
+
1 x 25

3 x 50
+
1 x 35

1. Power/Neutral Core :        
1.1 Conductors        
 

Nom. Cross sectional area
(i) Power cores (mm2)
(ii) Neutral cores (mm2)

16
25

25
25

35
25

50
35

  Max. D.C. resistance conductor at 20ºC
(i) Phase conductor (Ohm/Km)
(ii) Neutral conductor (Ohm/Km)
1.91
1.38
1.20
1.38
0.868
1.38
0.641
0.968
  Approx. diameter of conductor
(Compacted))

(i) Phase conductor (mm)
(ii) Neutral conductor (mm)
4.4
5.8
5.5
5.8
6.8
5.8
7.9
6.8
1.2 Insulation:
Minimum thickness:
(i) Phase conductor (mm)
1.0 1.0 1.0 1.2

2.

Messenger Wire(Bare):
(i) Nom. Cross sectional area (Sq. mm)
(ii) Approx. Tensile Strength (KN)

   

2.5
7.4

2.5
7.4

2.5
7.4

3.5
10.3

3.

Current Rating:
Continuous current carrying
capacity of cable in Air at
Ambient temp. 40ºC (Amp.)

60

76

92

110

4.

Approx. weight (Kg./Km.)

250

330

430

580

5.

Number of Cores:
(i)Power cores
(ii)Neutral cores messenger cores

(No.)    :  3
(No.)    :  1

6.

De-rating factor
De-rating factors for variation in Air Temp.
Air Temp. (ºC) Rating Factor
30 35 40 45 50 55
1.12 1.06 1.0 0.94 0.88 0.83

7.

(i) Identification of power core :
(ii) Laying :

By providing ridges on the insulation. Three Power cores and one Neutral core shall be suitable twisted around AAAC Messenger.

8.

Detail of the Power / Neutral core :
(i) Conductor:
a) Material
(b) Flexibility class as per IS:8130/84
(c) Form of Conductor
(ii) Insulation:
(a) Material
(b) Colour of Insulation

Aluminium to IS:8130/84
Class – 2
Compacted circular.

High Density Polyethylene to IS: 6474 - 1971 Black

9.

Details of the Messenger wire (Bare)
(i) Material
(ii) Form of Conductor

All Alloy Aluminium Conductor to IS:398(IV).
Standard compacted circular.

Top

 FINISHED AERIAL BUNCHED CABLE TESTING

Prior to dispatch, cable is subjected to rigorous testing. Test procedure followed at of works are according to various National & International specification and are covered in this paper.

Following tests are performed on Aerial Bunched Cables:

Test on Phase/Street lighting conductor

TESTS METHOD OF TESTING

Tensile Test

IS : 10810        pt – 2

Wrapping Test

IS : 10810        pt – 3

Conductor Resistance Test

IS : 10810        pt – 5

Test For thickness of Insulation

IS : 10810        pt – 6

Physical Test for polyethylene Insulation

Tensile Strength & Elong. Test
Melt flow Index
Vicat softening Point
Carbon Black Content & dispersion
Colour Fastness
Environmental stress cracking
Bleeding & Blooming
Volume Resistively Test



IS : 10810        pt – 7
IS : 10810        pt – 23
IS : 10810        pt – 22
IS : 10810        pt – 32
IS : 10810        pt – 18
IS : 10810        pt – 29
IS : 10810        pt – 19
IS : 10810        pt – 43

High Voltage test including water immersion test. IS : 1596

Test for messenger conductor:

Breaking load Test

IS : 398 (pt-IV)
Elongation Teat IS : 398 (pt-IV)
Resistance Test   IS : 398 (pt-IV)

Dimensional test as per the parameters specified in the technical particulars.
Bending test on completed cable shall also as performed. The diameter of mandrel shall be 10(D+d).

Where,
D = Overall diameter of the cable
d = Dia over conductor


 


Back
Top

 

Copyright 2006-08. All rights reserved by CapCab India Ltd.
Web Design & Search Engine Optimization By:
products Certificates Customers Enquiry Careers Contact Us About Us Home Sitemap