ACSR conductors consist of a solid or stranded steel core surrounded by strands of aluminum (E.C. GRADE). ACSR conductors are available in a wide range of steel, containing carbon from 0.5% to 0.85 %. The higher strength ACSR conductors are used for river crossings, overhead ground wires, installations involving extra long spans etc. Against any given resistance of conductor, ACSR may be manufactured for having a wide range of tensile strength as per the requirement.
The principal advantage of these conductors are high tensile strength so that they are used for longer spans with less supports. Due to the greater diameter of ACSR conductors a much higher corona limit can be obtained causing big advantages on high as well as extra high voltage overhead lines.
Sl. No.
Cond.
Area mm2
Stranding& Wire Dia in mm
Calculated sectional Area Sq.mm
Approx overall Dia mm
Weight
kg/km
Calc.
Electrical Resistance at 20oC Ohms/km
Approx
Calc.
Breaking Load(KN)
Alum.
Steel
Alum.
ACSR
ACSR
ACSR
Alum.
Steel
Cond.
Cond.
1
10
6/1.50
1/1.50
10.60
12.37
4.50
43
29
14
2.780
3.97
2
18
6/1.95
1/1.95
18.10
21.12
5.88
73
50
23
1.618
6.74
3
20
6/2.11
1/2.11
20.98
24.48
6.33
85
58
27
1.394
70.61
4
30
6/2.59
1/2.59
31.61
36.88
7.77
128
87
41
0.929
11.12
5
50
6/3.35
1/3.35
52.88
61.70
10.05
214
145
69
0.552
18.25
6
80
6/4.09
1/4.09
78.83
91.97
12.27
319
216
103
0.371
26.91
7
100
6/4.72
7/1.57
105.00
118.50
14.15
394
288
106
0.279
32.41
8
150
30/2.59
7/2.59
158.10
194.90
18.13
726
437
289
0.187
67.34
9
200
30/3.0
7/3.00
212.10
261.50
21.00
974
586
388
0.139
89.67
10
400
42/3.50
7/1.96
404.10
425.20
26.88
1281
1116
165
0.073
88.79
11
420
54/3.18
7/3.18
428.90
484.50
28.62
1621
1186
435
0.069
130.32
12
520
54/3.53
7/3.53
528.50
597.00
31.77
2004
1461
537
0.056
161.20
13
560
42/4.13
7/2.30
562.70
591.70
31.68
1787
1553
228
0.052
120.16